3.1 Input/Output Specifications
Item
Current
Output points per common
Surge absorber
Operating mode indicator
(Note 1)
The output method is selected by the software. The both polarities are off at the time of startup. The
output polarity must be set.
(Note 2)
This shows the response time when the push-pull method is set and the output current is 0.1 A. It
varies according to the setting of the output method and load.
(Note 3)
The voltages of the external power supply for the output circuit and the power supply for the load
circuit should be within the range of 5 to 24 V. When supplying power for the external power supply
and that for the load circuit from other power supplies, the load circuit voltage (V2) must be the same
as or smaller than the external supply voltage (V1). When the load circuit voltage (V2) is larger than
the external supply voltage (V1), the current flows back as below.
In the case of sink output
Internal circuit diagram and external connection diagram
Setting mode
Sink output
3-6
Specifications
100 mA or less
16 points/common (common to external power supply terminals)
Zener diode
LED display
Internal circuit diagram and external connection diagram
In the case of source output
WUME-FP7MXY-06