Two-wire output type
■
Precaution when Using LED-equipped Lead Switch
When an LED is connected in series to an input contact such as an LED-equipped lead switch,
make sure that the voltage applied to the PLC input terminal is greater than the ON voltage. In
particular, take care when connecting a number of switches in series.
■
Precaution when Using Two-wire Type Sensor
If input to the PLC does not turn off because of leakage current from a two-wire type
photoelectric sensor or a proximity sensor, connecting a bleeder resistor is recommended, as
shown below.
■
Precaution when Using LED-equipped Limit Switch
If the input of PLC does not turn off because of leakage current from the LED-equipped limit
switch, the use of a bleeder resistor is recommended, as shown below.
3.2.3 Output Wiring
The following figures show the case when they are connected with the sink output.
■
Protective circuit for inductive loads
With an inductive load, a protective circuit should be installed in parallel with the load.
WUME-FP7MXY-06
3.2 Wiring of Input and Output
3-9