Commissioning
NOTICE
!
Put system in safe operating mode
Never perform a firmware update during ongoing operation of the system in which the
product is installed. Before any firmware update, the system must first be properly shut
down or put in a safe operating state.
Note
Create backup before update
When you update your product's firmware, the state of your product before the update, in-
cluding the firmware used up to that point, can no longer be reconstructed unless a
firmware and configuration data backup exists.
Changes to settings require operator or admin rights. If you do not have these, the Set-
tings tab is grayed out and cannot be edited.
To update the firmware, you need a firmware container file: FWUPDATE.ZIP. You can get
it from the Downloads section of the WAGO website: ü http://www.wago.com.
Proceed as follows to update the firmware:
1. In the left-hand column of the WAGO I/O Field Webserver, click the Settings menu
item.
ð The Device configuration tab appears.
2. Select the Firmware upgrade tab.
3. Click the [Select file] button.
ð A file selection dialog opens.
4. Select the firmware container file FWUPDATE.ZIP from this dialog.
ð The name of the selected firmware container file appears in the File field.
5. Click the [Upgrade] button.
ð The firmware update is performed. After that, the port must be configured anew.
The firmware update procedure is as follows:
1. The firmware from the FWUPDATE.ZIP firmware container file is stored in the mod-
ule's flash memory.
2. An internal reset is triggered.
3. Then the device maintenance firmware starts; this edits the firmware container file
and installs the new firmware, including the module's configuration files.
4. You are notified when the installation procedure finishes.
5. The module then resets again.
6. The new firmware that has just been loaded starts.

10.3.1.4.5 Resetsetting the Module to the Factory Settings

In many cases, it can be helpful to reset the module to the factory settings. This can be
done for various selectable classes of settings with the Settings menu item on the Fac-
tory reset tab.
68
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A