750-655 [AS-Interface master module]
Data channel for parameter exchange
Response (Bus module)
Parameter
TGL_SM
A0 ... A7
PRM0 ...
PRM15
2.1.1.9.4.2

Setting the monitoring time (system parameters)

Request (Application)
Parameter
TGL_MS
PRM_RW
A0 ... A7
PRM0 ...
PRM15
Response (Bus module)
Parameter
TGL_SM
A0 ... A7
The module monitors the time for the transfer of the parameter data. The
monitoring of the time is started on the first occasion that the parameter range
specific to the module is accessed. It finishes with the receipt of the last
parameter word, which is identified by MORE_PRM = FALSE.
2.1.1.9.4.3

Restoring factory settings (system parameters)

Request (Application)
Parameter
TGL_MS
PRM_RW
A0 ... A7
Value
Meaning
== TGL_MS
Order executed
255
Address of parameter data length mirrored
N
Number of parameters in the address range 0 ... (n-1),
n ∈ {N < 250}
Value
Meaning
!= TGL_SM
Enter order
= TRUE
Write access
254
Address TIMEOUT
0 ... 65535
Monitoring time in milliseconds. The entry 0 means no
monitoring of the parameterization.
Value
Meaning
== TGL_MS
Order executed
254
Address TIMEOUT mirrored
Value
Meaning
!= TGL_SM
Enter order
= TRUE
Write access
255
Address of factory settings
WAGO-I/O-SYSTEM 750
I/O Modules