1MRS758755 C
3.18

Factory settings restoration

In case of configuration data loss or any other file system error that prevents the
protection relay from working properly, the whole file system can be restored to
the original factory state. All default settings and configuration files stored in the
factory are restored. For further information on restoring factory settings, see the
operation manual.
3.19

Load profile record LDPRLRC

3.19.1

Function block

Figure 108: Function block
3.19.2

Functionality

The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand
interval). Up to 12 load quantities can be selected for recording and storing in a
nonvolatile memory. The value range for the recorded load quantities is about eight
times the nominal value, and values larger than that saturate. The recording time
depends on a settable demand interval parameter and the amount of quantities
selected. The record output is in the COMTRADE format.
3.19.2.1
Quantities
Selectable quantities are product-dependent.
Table 211: Quantity Description
Disabled
IL1
IL2
IL3
Io
U12
Table continues on the next page
REC615 & RER615
Technical Manual
Quantity not selected
Phase 1 current
Phase 2 current
Phase 3 current
Neutral/earth/residual current
Phase-to-phase 12 voltage
Basic functions