Load Profile; Figure 11 Disturbance Records As Seen In "Admin" Mode - ABB Eagle Programming Manual

27 kv single phase recloser
Hide thumbs Also See for Eagle:
Table of Contents

Advertisement

settings Overwrite Enable is activated in DR settings page) That is, at any given point of
time, the EAGLE device shows the last 250 DRs.
The user will be able to download the DRs individually when logged in as an "Admin".

Figure 11 Disturbance Records as seen in "Admin" Mode

After Eagle issue the Final Open command latest Disturbance Record
may not be available to download. To download the records, energize
the Eagle and wait until Eagle save the Disturbance Records in proper
file format.

4.3.5. Load Profile

The load profile stores the historic load data captured at a periodic time interval. In EAGLE,
load profile function averages fundamental phase current, RMS current and maximum
RMS current and stores in a non-volatile memory. The value is recorded for an interval of
10 minutes with recording capability of last 90 days. The device will start averaging the
load data once it moves to healthy state and stops averaging once it detects insufficient
power/reboot.
The recloser will record at 10-minute intervals from 00:00 hour time. For example, if the
function is enabled or recloser is powered up at 08:12hrs, the first averaged data point is
recorded at 08:20hrs and first data point will be an average of 8 minutes instead of 10
minutes. Next data point will be recorded after 10 minutes at 08:30hrs. If insufficient
power/reboot is detected after a few hours at 10:35hrs which falls between two 10-minute
intervals, the ongoing data point will be recorded averaged over last 5 minutes.
20