No.
Name/Value
0.0 ... 3000.0 s
110.30
RO3 source
110.31
RO3 ON delay
Status of
selected
source
RO status
0.0 ... 3000.0 s
110.32
RO3 OFF delay
0.0 ... 3000.0 s
110.51
DI filter time
0.3 ... 100.0 ms
110.99
RO/DIO control
word
Bit
Name
0
RO1
1
RO2
2
RO3
3...7
Reserved
8
DIO1
9
DIO2
10...15 Reserved
0000h...FFFFh
111

111 Standard DIO, FI, FO

111.01
DIO status
Description
Deactivation delay for RO2.
Selects a signal to be connected to relay output RO3.
For the available selections, see parameter
source.
Note: For the cabinet-installed supply units, check the
delivery-specific use from the delivery-specific circuit
diagrams. Do not change the setting if relay output is in
use and connected already.
Defines the activation delay for relay output RO3.
t
t
On
Off
t
110.31 RO3 ON delay
On
t
110.32 RO3 OFF delay
Off
Activation delay for RO3.
Defines the deactivation delay for relay output RO3. See
parameter
110.31 RO3 ON
Deactivation delay for RO3.
Defines a filtering time for parameter
Note that this parameter has no effect on forced DI
values defined by parameters
Filtering time for 110.01.
Storage parameter for controlling the relay outputs and
digital input/outputs.
To control the relay outputs (RO) and the digital
input/outputs (DIO), send a control word with the bit
assignments shown below as Modbus I/O data. Set the
target selection parameter of that particular data. In the
source selection parameter of the desired output, select
the appropriate bit of this word.
Description
Source bits for relay outputs RO1...RO3 (see parameters 110.24,
110.27
and 110.30).
Source bits for digital input/outputs DIO1...DIO3 (see parameters
111.06
and 111.10).
RO/DIO control word.
Configuration of digital input/outputs and frequency
inputs.
Status of digital input/outputs DIO8...DIO1.
Example: 0000001001 = DIO1 and DIO4 are on, the
remainder are off.
110.24 RO1
1
0
1
0
Time
t
t
On
Off
delay.
110.01 DI
110.03
and 110.04.
Parameters 57
Def/FbEq16
10 = 1 s
MCB
0.0 s
10 = 1 s
0.0 s
10 = 1 s
status.
10.0 ms
10 = 1 ms
0000h
1 = 1
-

Advertisement

Table of Contents
loading

Table of Contents