3EM13853AF
Issue 01, September 2007
Trouble Analysis Procedures (TAPs)
TAP-100

Facility Alarm or Event

PURPOSE
This procedure provides instructions to clear a facility alarm or event.
GENERAL
In this procedure, x=port type and AID=individual port AID.
Refer to the 1677 SONET Link Address and Location Guide (PN 3EM13854AD) to determine facility
and module location and address.
STEP
PROCEDURE
Enter
1
Select alarm to clear. For facility alarms or events not listed, refer to IXL-101.
2
Facility Alarm or Event
and
RTRV-ALM-ALL;
RTRV-COND-ALL;
For ACTLPBK, go to step 3.
For AIC, go to step 6.
For AIS, go to step 7.
For AIS-L, go to step 8.
For AIS-P, go to step 9.
For AIS-V, go to step 10.
For APSB, go to step
For APSCCDFLTK, go to step 26.
For APSCIMP, go to step 28.
For APSCINCON, go to step 30.
For APSCM, go to step 31.
For APSCNMIS, go to step 54.
For BLSRAD-AUTO, go to step 64.
For BLSRAD-DUPNODE, go to step 65.
For BLSRAD-OSI-ERR, go to step 75.
For BLSRAD-TOPOERR, go to step 76.
For BP, go to step 89.
For CGAAIS, go to step 90.
For CGARED, go to step 91.
For CGAYEL, go to step 92.
For EOC, go to step 95.
For EOCL, go to step 95.
For FEAC alarms, go to step 96.
For FEPRLF, go to step 97.
For FRCKWKSWBK, go to step 98.
For FRCDWKSWPR, go to step 98.
and observe output.