3EM13853AF
Issue 01, September 2007
TAP-123

IMPROPRMVL Alarm

PURPOSE
This procedure provides instructions to clear an IMPROPRMVL alarm against a module.
GENERAL
IMPROPRMVL indicates a card was physically removed before being logically removed.
For information on TL1 command syntax, refer to the 1677 SONET Link Commands and Messages
manual (PN 3EM13852AF).
STEP
PROCEDURE
1
DANGER: Possibility of personal injury. Modules can be installed or removed with
rack power on. Hazardous electrical potentials are present; use extreme care when
installing or removing modules with power on.
WARNING: Possibility of equipment damage. Modules contain electrostatic-
2
sensitive devices (ESDs). These devices can be damaged by static discharge.
Refer to
Enter
3
Is removed card to be replaced?
4
Enter
5
Common cards (CCC, SSC, TC) are always assumed to be redundant and an alarm will
be outstanding if both cards are not present.
Go to step 9.
6
Refer to
7
Go to step 9.
8
9
STOP. This procedure is complete.
IMPROPRMVL Alarm
Introduction
for special handling instructions.
and
RTRV-ALM-ALL;
RTRV-COND-ALL;
If no, go to step 5.
If yes, go to step 7.
to delete card and remove it from equipment database.
DLT-EQPT::AID;
IXL-103
for card replacement procedures.
to retrieve all alarms and conditions.
TAP-123
4-67