Alcatel-Lucent 1677 SONET Maintenance And Trouble Clearing page 146

Hide thumbs Also See for 1677 SONET:
Table of Contents

Advertisement

TAP-127
Did output return COMPLD or DENY?
9
Enter
10
where: AID=Equipment access identifier of card with FWMISM alarm
Did command return COMPLD or DENY?
11
Enter
12
where: AID=Equipment access identifier of card with FWMISM alarm
Did output return COMPLD or DENY?
13
Enter
14
Observe output. Did FWMISM alarm clear?
15
Replace module reporting FWMISM alarm. Refer to
16
replacement procedure.
Enter
17
Did FWMISM clear?
18
Contact next level of technical support for assistance.
19
20
STOP. This procedure is complete.
4-78
If COMPLD, go to step 10.
If DENY, go to step 19.
INIT-SYS::AID:::;
If COMPLD, go to step 12.
If DENY, go to step 19.
.
RST-EQPT::AID;
If COMPLD, go to step 14.
If DENY, go to step 19.
and
RTRV-ALM-ALL;
RTRV-COND-ALL;
If yes, go to step 20.
If no, go to step 16.
and
RTRV-ALM-ALL;
RTRV-COND-ALL;
If yes, go to step 20.
If no, go to step 19.
Issue 01, September 2007
to retrieve all alarms and conditions.
IXL-103
for the correct module
to retrieve all alarms and conditions.
3EM13853AF
FWMISM Alarm