Fan Faults (Clfan, Ctrlread, Ctrlwrite, Int) - Alcatel-Lucent 1677 SONET Maintenance And Trouble Clearing

Hide thumbs Also See for 1677 SONET:
Table of Contents

Advertisement

3EM13853AF
Issue 01, September 2007
TAP-110

Fan Faults (CLFAN, CTRLREAD, CTRLWRITE, INT)

PURPOSE
This procedure provides instructions to clear a fault indication for the fan-tray assembly.
GENERAL
The fan-controller card monitors the rotational speed of each fan. When all fans rotate at the correct
speed, the
light, on the common control card, is green to indicate the fan tray is working.
FAN
If one fan fails, the
FAN
72 hours to maintain n+1 protection.
If two or more fans fail, the
immediately to prevent the node from overheating.
CLFAN indicates failure of one or more fans in the fan tray.
CTRLREAD indicates fan controller read operation failure. CTRLWRITE indicates fan controller
write operation failure.
INT indicates unrecognized fan controller.
STEP
PROCEDURE
Refer to
1
fan-tray assembly.
2
STOP. This procedure is complete.
Fan Faults (CLFAN, CTRLREAD, CTRLWRITE, INT)
light turns amber; this indicates the fan tray must be replaced within
light turns red; this indicate the fan-tray module must be replaced
FAN
DLP-132
to replace 15RU fan-tray assembly or
TAP-110
DLP-145
to replace 18RU
4-43