TAP-137

FACTERM Alarm

PURPOSE
This procedure provides instructions to clear a FACTERM alarm against an IOC module.
GENERAL
FACTERM indicates facility/circuit termination equipment failure.
For information on TL1 command syntax, refer to the 1677 SONET Link Commands and Messages
manual (PN 3EM13852AF).
STEP
PROCEDURE
1
DANGER: Possibility of personal injury. Modules can be installed or removed with
rack power on. Hazardous electrical potentials are present; use extreme care when
installing or removing modules with power on.
WARNING: Possibility of equipment damage. Modules contain electrostatic-
2
sensitive devices (ESDs). These devices can be damaged by static discharge.
Refer to
Enter
3
Observe output. Note module with FACTERM alarm.
4
Are FACTERM alarms declared against both the ACTIVE and STANDBY IOC
5
modules in a protection pair?
Enter
6
where: AID=Equipment access identifier of card with FACTERM alarm
Did command return COMPLD or DENY?
7
Reset card with FACTERM alarm.
8
FACTERM Alarm
Introduction
for special handling instructions.
and
RTRV-ALM-ALL;
RTRV-COND-ALL;
If yes, go to step 18.
If no, go to step 6.
RMV-EQPT::AID;
If COMPLD, go to step 8.
If DENY, go to step 18.
to retrieve all alarms and conditions.
TAP-137
4-95