3EM13853AF
Issue 01, September 2007
TAP-136

PRCDRERR Alarm

PURPOSE
This procedure provides instructions to clear a PRCDRERR alarm against a TC, DS0G, DS3, ECC,
EDFA, GIGE, OC3, OC12, OC48, OC192, TMUX, or VSC card.
GENERAL
PRCDRERR indicates physically equipped module is inconsistent with slot provisioning.
For information on TL1 command syntax, refer to the 1677 SONET Link Commands and Messages
manual (PN 3EM13852AF).
STEP
PROCEDURE
1
DANGER: Possibility of personal injury. Modules can be installed or removed with
rack power on. Hazardous electrical potentials are present; use extreme care when
installing or removing modules with power on.
WARNING: Possibility of equipment damage. Modules contain electrostatic-
2
sensitive devices (ESDs). These devices can be damaged by static discharge.
Refer to
Enter
3
Observe output. Note module with PRCDRERR alarm.
4
Replace card with PRCDRERR alarm. Refer to
5
procedures.
Enter
6
Did PRCDRERR clear?
7
Contact next level of technical support for assistance.
8
9
STOP. This procedure is complete.
PRCDRERR Alarm