Prepare to Remove an SP
1.
Determine which SP requires service.
See
"Identify Faulted Components" on page 36
Ensure that the SPM on the SP is not managing hardware.
2.
-> show /System/Other_Removable_Devices/Service_Processors/
Service_Processor_x/Service_Processor_Module_0 state_sp
Properties:
state_sp = OffDuty
If state_sp reports OffDuty, the SP is not the Active SP and you can continue to
■
If state_sp reports Running, you must first change the Active SP assignment. See
■
Which SP Is Managing System Activity" on page
Note -
step for the second SPM. For example, if you previously ran the state_sp command
on Service_Processor_0/Service_Processor_Module_0, you now need to run it on
Service_Processor_0/Service_Processor_Module_1.
3.
For SPARC M8-8 and SPARC M7-8 servers only, verify that the PCIe devices are
offline.
■
For SPARC M8-8 and SPARC M7-8 servers with two PDomains, check the
state for both SPMs.
-> show /System/Other_Removable_Devices/Service_Processors/
-> show /System/Other_Removable_Devices/Service_Processors/
For SPARC M8-8 and SPARC M7-8 servers with one PDomain, check the
■
state for the only SPM.
-> show /System/Other_Removable_Devices/Service_Processors/
If state_pcie returns a value of Online, log onto the host that contains the SPM and prepare
the PCIe card for removal by taking the devices offline for the appropriate SP/SPM slot. See
"Servicing PCIe Cards" on page
126
SPARC M8 and SPARC M7 Servers Service Manual • September 2017
For SPARC M8-8 and SPARC M7-8 servers with two PDomains, perform this
Service_Processor_x/Service_Processor_Module_0 state_pcie
Properties:
state_pcie = Offline
Service_Processor_x/Service_Processor_Module_1 state_pcie
Properties:
state_pcie = Offline
Service_Processor_x/Service_Processor_Module_0 state_pcie
Properties:
state_pcie = Offline
and
"SP General Status LEDs" on page
124.