Application Macro 3-wire

This macro is intended for those applications where the drive is controlled using momentary push-
buttons. It gives two more preset speeds compared to Factory Macro (1) by using DI4 and DI5.
The value of parameter 9902 is 2 (3-
Input signals
• Start, stop and direction
(DI1,2,3)
• Analog reference (AI1)
• Preset speed selection (DI4,5)
*Constant speed selection: 0 = open, 1 = connected
Note! Stop input (
DI
Application Macro 3-wire parameter values:
1001
EXT
1002
EXT
1003
DIRECTION
1102
EXT
1103
EXT REF
1105
EXT REF
1106
EXT REF
1201
CONST SPEED SEL
1401
RELAY OUTPUT
ACS 400 User's Manual
WIRE
Output signals
DI4
DI5
0
1
0
1
2) deactivated: panel START/STOP button interlocked (local).
1
4 (
COMMANDS
DI
2
0 (
COMMANDS
NOT SEL
3 (
REQUEST
1/
2
6 (
EXT
SEL
EXT
1
1 (
SELECT
AI
1
60 Hz
MAX
2
0 (
SELECT
KEYPAD
8 (
DI
1
3 (
FAULT
http://nicontrols.com
).
• An. output AO: Frequency
• Relay output 1: Fault
• Relay output 2: Running
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Momentary activation with DI2 activated: Start
Momentary deactivation: Stop
Activate to reverse rotation: Fwd/Rev
Constant speed selection*
Constant speed selection*
Relay output 1, programmable
Default operation: fault => 17 connected to 18
Relay output 2, programmable
Default operation: running => 20 connected to 22
Output
0
Reference through AI1
0
Constant speed 1 (1202)
1
Constant speed 2 (1203)
1
Constant speed 3 (1204)
1
,2
,3)
1402
P
P
RELAY OUTPUT
)
1503
AO CONTENT MAX
)
1601
RUN ENABLE
1)
1604
FAULT RESET SEL
1)
2008
MAXIMUM FREQ
2105
PREMAGN SEL
)
2201
/
ACC
DEC
4,5)
4001
PID GAIN
(-1))
4002
PID INTEG TIME
Jumper Setting
2
2 (
)
RUN
60 Hz
0 (
)
NOT SEL
0 (
)
KEYPAD
60 Hz
0 (
)
NOT SEL
1/2
0 (
)
SEL
NOT SEL
1.0
60 s
57