Safe Torque Off Operating Guide • An asterisk (*) indicates a default setting of a describes how to use Danfoss drives in functional parameter. safety applications. This manual is supplied with the drive when the safe torque off option is present.
This section provides a brief description of the various The aim of the directive is to ensure personal safety and approvals and certifications that are found on Danfoss avoid property damage when operating electrical drives. Not all approvals are found on all drives.
Page 10
1 of more marine certification societies in order guide, the equipment meets the UL standards for electrical ® to receive a regulatory license and insurance. Danfoss VLT and thermal safety. This mark certifies that the product AQUA Drive series drives are certified by up to 12 different performs to all required engineering specifications and marine classification societies.
Page 16
As a response to a critical level, the drive adjusts the Danfoss does not recommend using this feature for 525– switching frequency. For high internal temperatures and 690 V drives connected to an IT mains network.
Page 19
Product Features Design Guide When matching drive and motor, Danfoss specifies the • Sine-wave filter is required when following extra requirements to ensure adequate motor Long cables (voltage peaks) or increased thermal protection: mains voltage produce voltages • Do not exceed the maximum allowed ratio exceeding the maximum allowable between drive size and motor size.
Built-in, high-performance switch enabling line- file. topology, which eliminates the need for external • Acyclic parameterization using PROFIBUS DP-V1, switches. PROFdrive, or Danfoss FC profile state machines. • DLR Ring (from October 2015). • Advanced switch and diagnosis functions. 6.1.2 VLT ®...
The resistor is selected based on its ohmic value, its power and ground. dissipation rate, and its physical size. Danfoss offers a wide variety of different resistors that are specially designed to Installed around the 3 motor phases (U, V, W), the Danfoss drives.
Page 35
If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
Page 38
If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
Cables with a large cross-section. elevation 1000 m (3300 ft) above sea level. See chapter 9.6 Derating for detailed information on If these conditions are present, Danfoss recommends derating. stepping up 1 power size. The drive utilizes a back-channel cooling concept that 9.6.1 Derating for Low-Speed Operation...
Page 73
K), 91% of the rated output current is available. 9.6.3 Derating for Ambient Temperature and Switching Frequency NOTICE FACTORY DERATING Danfoss drives are already derated for operational temperature (55 °C (131 °F) T and 50 °C (122 °F) T AMB,MAX AMB,AVG Use the graphs in Table 9.3 to Table 9.4 to determine if the output current must be derated based on switching frequency...
Illustration 10.4. Remember to connect the shields in a proper way to ensure optimum electrical immunity. The load sharing feature requires extra equipment and safety considerations. Consult Danfoss for ordering and • Isolate control wiring from high-power cables. installation recommendations.
Use a dU/dt or sine-wave filter. cations, use the motor insulation ratings shown in 10.7 Braking Table 10.10. If a motor has lower insulation rating, Danfoss recommends using a dU/dt or sine-wave filter. 10.7.1 Brake Resistor Selection Nominal mains voltage...
Page 85
Table 10.12 Braking Capability, 525–690 V 107780 200V : R = Ω motor Danfoss offers brake resistors with duty cycle of 5%, 10%, 464923 500V : R = Ω and 40%. If a 10% duty cycle is applied, the brake resistors...
If the brake IGBT is overloaded or overheated, the relay/digital signal from the brake to the drive turns off the brake IGBT. This relay/digital signal does not protect against a short circuit in the brake IGBT. Danfoss recommends a means to disconnect the brake if a short circuit occurs in the brake IGBT.
25 m switching frequency. Whether the switching frequency is (82 ft), Danfoss recommends setting parameter 14-50 RFI detected depends on the type of RCD used. Filter to [ON]. Refer also to the Application Note, VLT on IT Mains.
Page 94
The immunity requirements for drives depend on the installation environment. The requirements for the industrial environment are higher than the requirements for the home and office environment. All Danfoss drives comply with the requirements for both the industrial and the home/office environment.
Page 100
• Total cost of ownership (initial cost, efficiency, and maintenance). 10.16.6 Harmonic Calculation Use the free Danfoss MCT 31 calculation software to determine the degree of voltage pollution on the grid and needed ® precaution. The VLT Harmonic Calculation MCT 31 is available at www.danfoss.com.
11 Basic Operating Principles of a Drive 11.2 Drive Controls This chapter provides an overview of the primary assemblies and circuitry of a Danfoss drive. It describes the The following processes are used to control and regulate internal electrical and signal processing functions. A...
Pipe-fill mode can be enabled to prevent water which is normally 30 Hz. hammering. The Danfoss drive can fill the vertical pipes • The motor reactance is nonlinear in submersible using the PID controller to ramp up the pressure slowly pump motors and, therefore, automatic motor with a user-specified rate (units/second).
This All Danfoss drives have built-in DC coils in the DC link to regenerative brake power increases the DC-link voltage have a high-power factor and reduce the THD on the main and a brake chopper ensures that the power is transmitted supply.
Page 136
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.