Online Connection Via Profinet Interface; Using The Profinet Io Interface; Online Access Via Profinet - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

7. In order to search for the drive unit with the set parameters, click "Start search".
The devices that are found are displayed in the table of results.
8. Select your drive unit from the table.
9. To establish an online connection to the drive unit, click "Connect".
Result
An online connection has been established between the PG/PC and the drive unit. The
settings are used automatically the next time you go online and the "Go online" dialog is no
longer displayed.
4.5.4

Online connection via PROFINET interface

4.5.4.1

Using the PROFINET IO interface

Establishing an online connection between the PG/PC and the drive unit via a PROFINET interface
The PROFINET interface of the CU320-2 PN is the X150. The drive and PG/PC must be
located in the same subnet in order to establish an online connection. Correspondingly, you
must select the IP address and subnet mask.
To establish an online connection between a PG/PC and an individual drive, proceed as
follows:
1. Search for a device using the online access
2. Assign the device an IP address and device name.
3. Adapt the IP address and subnet mask of the configured device in the project.
4. Compare the assigned interface data with the configured interface data.
4.5.4.2

Online access via PROFINET

Use online access
Get the TIA Portal to search for the drive via the online access of your computer.
Preconditions
● You have inserted a CU320-2 PN Control Unit.
● There is a connection between the Ethernet interface of your PG/PC and the PROFINET
interface of your drive (X150).
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
4.5 Establishing an online connection to the drive
Commissioning
133

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents