Configuration - BONFIGLIOLI ACTIVE CUBE 201 Operating Instructions Manual

Frequency inverter 230 v/400 v, 0.25 kw...132 kw
Hide thumbs Also See for ACTIVE CUBE 201:
Table of Contents

Advertisement

WARNING
For control of a synchronous machine and setting parameter
"510 - FOC Syn. Speed Controlled , you will have to cancel the guided commissioning
first by pressing the ESC key after the "SEtUP" message and set parameter
382. To do this, proceed according to the operating instructions for the extension
module EM-RES or EM-ABS-01 installed. Otherwise, personal or machine damage may
occur.
When the unit is in "as-delivered" condition, the guided commissioning procedure
is started automatically. After successful commissioning, the guided commissioning
can be carried out again later via the sub-menu CTRL.
Use the ENT key to switch to the CTRL sub-menu.
In the CTRL sub-menu, select the menu item "SetUP" and confirm by pressing the
ENT key.
Use the ENT button to select parameter
The available configurations are displayed automatically depending on the selected
28.
Control Level
Use the arrow keys to enter the number of the required configuration. (for a
description of the configurations, refer to the following chapter)
If the setup was changed, the hardware and software functionality will be
configured. The message "SEtUP" is displayed again.
Confirm this message by pressing the ENT key in order to continue the
commissioning procedure.
Switch to the next parameter.
After initialization, confirm the selected configuration by pressing the ENT key.
Continue the guided commissioning procedure according to the following chapters.
9.2.1

Configuration

30 determines the assignment and basic function of the control inputs and outputs as
Configuration
well as the software functions. The software of the frequency inverter offers several configuration
options. These differ with respect to the way in which the drive is controlled. Analog and digital
inputs can be combined and complemented by optional communication protocols as further
reference value sources. The Operating Instructions describe the configurations and relevant
parameters on the third
comply with the following manuals:
Manual
Application Manual – Electronic Gear
Application Manual: Positioning
Application Manual – Hoisting Gear Drives
Configuration 110, sensor-less control (SLC)
Configuration 110 contains the functions for variable-speed control of a 3-phase
machine in a wide range of standard applications. The motor speed is set according
to the V/f characteristic in accordance with the voltage/frequency ratio.
100
Configuration
28 (Set parameter
Control Level
Operating Instructions ACU
30.
28 to value 3). Please also
Control Level
Configuration
(x15, x16)
(x40)
(x60)
30 to
Configuration
Offset
E N T
E N T