18.5.3.3 Limit value sources

The limitation of the frequency can be done by setting fixed values and by linking to an analog input
parameter. The analog value is limited via parameters
Maximum Reference Percentage
the reference percentage value channel.
The assignment is done for the torque controller via parameters
and
Frequency Lower Limit Source
Operation mode 769, 770
101 - Analog Input MFI1A
110 - Fixed Limit
201 - Inv. Analog Input MFI1A
210 - Inv. Fixed Limit

18.5.3.4 Switching over between speed control and torque control

With the signal assigned to parameter
speed control and torque control. See Chapter 16.4.6 "16.4.6".
18.5.4

Speed controller

The actual speed source is selected via parameter
Speed Sensor 1 is used as the source of actual speed. If Speed Sensor 2 of an extension module is
to deliver the actual value signal for the speed controller, Speed Sensor 2 must be selected as the
source. Alternatively, the speed controller can derive the actual speed value from the machine model
in in Configurations 410, 411 and 430 (
Operation Mode 766
1 - Speed Sensor 1
2 - Speed Sensor 2
3 - Machine Model
Speedtracking EC
4 -
1
Speedtracking EC
5 -
2
1)
Only available if extension module is installed
The control of the torque-forming current components is done in the outer control loop by the speed
controller. Via parameter
controller. The operation mode defines the use of the parameterizable limits. These are referred to
the direction of rotation and the direction of the torque and depend on the selected configuration.
226
519, but does not consider the
770.
Multifunction input 1 in analog Operation Mode 452 is the
source.
The selected parameter values are taken into account to limit
the speed controller.
Operation mode 101, inverted.
Operation mode 110, inverted.
n-/M-Control Change-Over
Parameter Configuration
The actual speed source is speed sensor 1 of the basic device (factory
setting).
The actual speed source is speed sensor 2 of an extension module.
The speed controller receives the calculated actual speed value from the
machine model. Can be set in configurations 4xx and 6xx.
Speedtracking by comparison between the calculated machine model and
speed sensor 1 to increase speed accuracy. Can be set in configurations 4xx
and 6xx. The setting for parameter
considered.
Speed compensation by comparison between the calculated machine model
and speed sensor 2 of an extension module
Can be set in configurations 4xx and 6xx. The setting for parameter
Integral Time Speedtracking
720, you can select the operation mode for the speed
Operation Mode
Operating Instructions ACU
Minimum Reference Percentage
Gradient Percentage Ramp
Frequency Upper Limit Source
Function
164, you can switch between
766. In the default setting,
Actual Speed Source
30).
Function
Integral Time Speedtracking
1)
to increase speed accuracy.
515 is considered.
518 and
477 of
769
1)
515 is
12/16

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACTIVE CUBE 201 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Active cube 501Active cube 401Active cube 601

Table of Contents