Scaling; Digital Outputs - BONFIGLIOLI ACTIVE CUBE 201 Operating Instructions Manual

Frequency inverter 230 v/400 v, 0.25 kw...132 kw
Hide thumbs Also See for ACTIVE CUBE 201:
Table of Contents

Advertisement

16.2.2.1 Scaling

The repetition frequency mode for the multifunction output corresponds to the emulation of an
incremental sensor. Parameter
output. The minimum frequency of Repetition Freq. Operation is 30 Hz. Smaller values will be output
as 0 Hz.
The pulse-pause ratio is not 1:1. For this reason, Repetition Freq. Operation should only be
evaluated with the rising or falling edge in the evaluation device.
Parameter
No.
Description
556 Division Marks
The frequency limit of f
556.
Marks
16.3

Digital Outputs

Op. Mode Digital Output 1
link the digital outputs to various functions. The selection of the functions depends on the
parameterized configuration. When multifunction output MFO1 is to be used as a digital output, an
550 must be selected and linked via parameter
Operation Mode
Operation mode 530, 532,
554
0 - off
1 - Ready or Standby Signal
2 - Run Signal
3 - Error Signal
4 - Setting Frequency
Reference frequency
5 -
reached
Reference percentage
6 -
reached
7 - Ixt warning
Warning Heat Sink
8 -
Temperature
9 - Inside temperature warning
10 - Motor temperature warning
11 - General warning
12 - Warning overtemperature
13 - Mains failure
Warning motor circuit
14 -
breaker
12/16
Division Marks
Min.
30
=150 kHz must not be exceeded in the calculation of parameter
max
S
max
Frequency
530 and the relay output with parameter
Digital output is switched off
Frequency inverter is initialized and on stand-by or in operation
Signal enable STO (S1IND/STOA and S7IND/STOB) and a start
command are present, output frequency available.
Message is displayed via parameter Current Error 259 and
Warnings 269.
The Stator Frequency 210 is higher than the parameterized
Setting Frequency 510.
The Actual Frequency 241 of the drive has reached the Internal
Reference Frequency 228.
The Actual Percentage Value 230 has reached the Reference
Percentage Value 229.
The Warning Limit Short Term Ixt 405 or Warning Limit Long
Term Ixt 406 were reached.
Max. heat sink temperature T
Heat Sink Temp.
Max. Inside Temperature T
Inside Temp.
Waring behavior as per configured Motor Temp. Operation Mode
570 at max. motor temperature T
Message is displayed via parameter Warnings 269.
The selected Warning Limit Heat Sink Temp. 407, Warning Limit
Inside Temp. 408 or maximum motor temperature were
exceeded.
Failure of the mains voltage and power regulation active
according to Operation Mode 670 for the voltage controller.
Parameterized Operation Mode 571 for motor circuit breaker
was triggered.
Operating Instructions ACU
556 must be set according to the frequency to be
Setting
Max.
8192
150000
Hz
value
Op. Mode Digital Output 3
Digital Operation
Function
of 80 °C minus Warning Limit
K
407 reached.
of 65 °C minus Warning
i
408 reached.
PTC .
Factory setting
1024
Division
532
554.
Limit