Stopping behavior
Coast to stop
Stopping behavior 1
Stop
+ off
Stopping behavior 2
Stop + Hold
Stopping behavior 3
Stop + DC brakes
Stopping behavior 4
emergency stop
+ off
Stopping behavior 5
Emergency stop + hold
Stopping behavior 6
Emergency stop + DC
brakes
Stopping behavior 7
DC brake
Please refer to Chapter 16.3.5 "16.3.5" for information on mechanical brake control.
When a synchronous motor is connected, BONFIGLIOLI VECTRON MDS GmbH recommends setting
630 = 22.
Operation Mode
12/16
Stopping behavior
The inverter is disabled immediately. The drive deenergized immediately
and coasts freely.
The drive is brought to a standstill at the set deceleration. As soon as
the drive is at a standstill, the inverter is disabled after a after a holding
time. The holding time can be set via parameter
Depending on the setting of parameter
623 will be impressed or the
Starting Current
be applied.
The drive is brought to a standstill at the set deceleration and remains
permanently supplied with current.
Depending on the setting of parameter
623 will be impressed as from standstill, or the
Starting Current
600 will be applied.
Starting Voltage
In Configurations 2xx, the magnetizing current is used instead of the
623. The magnetizing current results from
Starting Current
716 and
Magnetising Current
The drive is brought to a standstill at the set deceleration. As from
standstill, the DC set via parameter
for the
632.
Braking Time
Comply with the notes in chapter "Direct current brake".
Stopping behaviors 3, 6 and 7 are only available in the configurations of
sensor-less V/f control (1xx).
The drive is brought to a standstill at the emergency stop deceleration.
As soon as the drive is at a standstill, the inverter is disabled after a
after a holding time.
The holding time can be set via parameter
Depending on the setting of parameter
623 will be impressed or the
Starting Current
be applied as from standstill.
The drive is brought to a standstill at the emergency stop deceleration
and remains permanently supplied with current.
Depending on the setting of parameter
623 will be impressed or the
Starting Current
be applied as from standstill.
The drive is brought to a standstill at the set emergency stop
deceleration. As from standstill, the DC set via parameter
631 is impressed for the
Current
Comply with the notes in chapter "Direct current brake".
Stopping behaviors 3, 6 and 7 are only available in the configurations of
sensor-less V/f control (1xx).
DC braking is activated immediately. The direct current set with the
parameter
Braking Current
Comply with the notes in chapter "Direct current brake".
Stopping behaviors 3, 6 and 7 are only available in the configurations of
sensor-less V/f control (1xx).
Operating Instructions ACU
Holding Time
Starting Function
Starting Voltage
Starting Function
Reduction Factor Flux
Braking Current
Holding Time
Starting Function
Starting Voltage
Starting Function
Starting Voltage
632.
Braking Time
631 is impressed for the
638.
620, the
600 will
620, the
the Rated
778.
631 is impressed
638.
620, the
600 will
620, the
600 will
Braking
632.
Braking Time