BONFIGLIOLI ACTIVE CUBE 201 Operating Instructions Manual page 169

Frequency inverter 230 v/400 v, 0.25 kw...132 kw
Hide thumbs Also See for ACTIVE CUBE 201:
Table of Contents

Advertisement

The following characteristic is set by default and can be adapted to the application via the
parameters mentioned.
Y
(X2=98%/Y2=100%)
pos. maximum value
50 Hz
(X1=2%/Y1=0%)
0 V
0.2 V
(0 mA)
neg. maximum value
The freely configurable characteristic enables setting a tolerance at the ends as well as a reversal of
the direction of rotation.
The following example shows the inverse reference value specification with additional reversal of the
direction of rotation. This is often used in pressure control systems.
Y
pos. maximum value
50 Hz
(X1=2%/Y1=100%)
0 V
0.2 V
(0 mA)
5.5 V
-40 Hz
(X2=98%/Y2=-80%)
The definition of the analog input characteristic can be calculated via the two-point form of the line
equation. The speed Y of the drive is controlled according to the analog control signal X.
12/16
Point 1:
X1
2,00%
Y1
0,00%
Point 2:
X2
98,00%
9.8 V
Y2
10
0,00%
X
+10 V
(+20 mA)
Point 1:
X1
2,00%
Y1
10
0,00%
Point 2:
+10 V
X2
98,00%
(+20 mA)
Y2
8
0,00%
X
9.8 V
The change of direction of rotation is done in this
example at an analog input signal of 5.5 V. pos./neg.
maximum figure
Y2
-
Y1
Y
X
X2
-
X1
Operating Instructions ACU
10
V
0,20
V
50,00
Hz
0,00
Hz
10
V
9,80
V
50,00
Hz
5
0,00
Hz
10
V
0,20
V
50,00
Hz
50,00
Hz
10
V
9,80
V
50,00
Hz
4
0,00
Hz
X1
Y1
169