16.4.10 Handshake Traverse Function

Via Parameter
Handshake Traverse Function 49
direction of rotation of the slave drive of the traverse function. The Traverse Function is switched on
via parameter
Operation Mode

16.4.11 User Warning

For parameterization of external warnings, you can use parameters
1364 . Parameterization of an a user warning error enables triggering a warning in the
Warnig 2
device via a digital signal in the event of a critical state. This warning is displayed in
273 can be transmitted to a higher-level control. Please also refer to parameter
Warnings
626 and the explanations in Chapter "".
Appl. Warning Mask
2 independent warnings can be parameterized via

16.4.12 External Error

Parameterization of an external error enables switching off or shutting down several frequency
inverters at a time if a fault occurs in the plant or the drive. If an error occurs in a frequency inverter,
the error signal can be transmitted via a bus system and the required reaction can be triggered in
another frequency inverter. Parameter
input signal which is to trigger the external error.
Via Parameter
Op Mode ext. Error
Operation Mode 535
0 - disabled
1 - Error switch-off
2 - Shutdown, error
Emergency-stop,
3 -
error
For parameterization of external warnings, you can use parameters
1364 . Please refer to Chapter 16.3.9 "16.3.9" for more details.
Warnig 2
16.5

Function Modules

16.5.1

Timer

The timer function can be linked to various functions for time-control of digital signals.
Parameters
Operation Mode Timer 1
of the digital input signals and the unit of time of the time function.
Operation mode Timer 790,
793
0 - off
1 - Normal, Rising Edge, Sec.
12/16
1
Output value drops at set ramp
1
Output value is reset to initial value
1 = Contact closed
435.
External Error
535 the response to an external error can be configured.
No response to external errors.
The drive is switched off and the error message „F1454 External Error" is
output if the logic signal or digital input signal for parameter
183 is present.
Error
The drive is stopped at the current deceleration ramp and the error
message „F1454 External Error" is output if the logic signal or digital
input signal for parameter
The drive is stopped at the current emergency stop ramp and the error
message „F1454 External Error" is output if the logic signal or digital
input signal for parameter
790 and
Signal output is switched off.
Positive signal edge starts timer (trigger), 
 time 1 delays the
output signal, 
 time 2 defines the signal period
Operating Instructions ACU
the signal source is selected for specification of the
User Warnig 1
1363 and
User Warnig 1
183 can be assigned the logic signal or digital
Function
183 is present.
External Error
183 is present.
External Error
User Warnig 1
Operation Mode Timer 2
Function
1363 and
User
Application
Create
1364.
User Warnig 1
External
1363 and
User
793 define the evaluation
195

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACTIVE CUBE 201 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Active cube 501Active cube 401Active cube 601

Table of Contents