In this example, parameter
Gear Factor Denominator
For optimum motor control, BONFIGLIOLI VECTRON MDS GmbH recommends
installing a speed sensor directly at the motor.
11.4.4

Filter time constant, Speed Sensor 1

EC1 Filter time constant
can be used in situations where the speed sensor fluctuates (e.g. for mechanical reasons).
BONFIGLIOLI VECTRON MDS GmbH recommends changing the value in small steps and checking
the individual results. Do not change the value in great steps.
Parameter
No.
Description
1193 EC1 Filter time constant
12/16
EC1 Gear Factor Numerator
512 must be set to 1.
1193 can be used in order to filter the speed of speed sensor 1. This filter
Min.
Operating Instructions ACU
511 must be set to 2 and parameter
Setting
Max.
0 us
32000 us
EC1
Factory setting
0 us