11.2.3

Magnetizing Current

The
Rated Magnetising Current
which is present at the machine in no-load condition depending on the speed. The guided
commissioning determines this value at approx. 30% of the
compared to the field current of an externally excited direct current machine.
In order to optimize the sensorless field-oriented control system, the machine must be operated
without load at a rotational frequency which is below the
optimization increases with the adjusted
operation. The flux-forming actual current value
set
Rated Magnetising Current
The field-oriented control with speed sensor feedback uses the parameterized
716 for the flux in the motor.
Current
The dependence of the magnetizing on the frequency and voltage at the corresponding operating
point in question is taken into account by a magnetizing characteristic. The characteristic is
calculated via three points, in particular in the field weakening area above the rated frequency. The
parameter identification has determined the magnetizing characteristic and set the parameters
Magnetising Current 50% Flux
715 .
110% Flux
Parameter
No.
Description
713 Magnetizing current 50%
714 Magnetizing current 80%
715 Magnetizing current 110%
716 Rated magnetizing current
11.2.4

Rated slip correction factor

The rotor time constant results from the inductance of the rotor circuit and the rotor resistance. Due
to the temperature-dependence of the rotor resistance and the saturation effects of the iron, the
rotor time constant is also dependent on temperature and current. The load behavior and thus the
rated slip depend on the rotor time constant. The guided commissioning determines the machine
data during the parameter identification and sets the parameter
accordingly. For the fine adjustment or a check of the rotor time constant, proceed as follows: Load
the machine at fifty percent of the
approximately fifty percent of the
case, the correction factor must be changed accordingly. The larger the correction factor is set, the
stronger the voltage drop when the machine is loaded. The software-calculated rotor time constant
value can be read via actual value
a winding temperature which is also reached during normal operation of the motor.
Parameter
No.
Description
718 Rated slip correction factor
12/16
716 is a measure of the flux in the motor and thus of the voltage
Switching Frequency
215 to be read out should roughly match the
Isd
716.
713,
Magnetising Current 80% Flux
Min.
1.00 %
1.00 %
110.00 %
0.01I
FIN
Rated Frequency
370 with a max. deviation of 5%. If this is not the
Rated Voltage
Act. Rotor Time Constant
Min.
0.01 %
Operating Instructions ACU
371. This current can be
Rated Current
375. The accuracy of the
Rated Frequency
400 and when the drive is in no-load
714
and Magnetising Current
Setting
Max.
Factory setting
50.00 %
80.00 %
197.00 %
oI
FIN
Rated Slip Correction Factor
375. As a result, the voltage must be
227. The adjustment should be done at
Setting
Max.
Factory setting
300.00 %
Rated Magnetising
31.00 %
65.00 %
145.00 %
0.3I
FIN
718
100.00 %
123