16.1.1.2 Scaling

The analog input signal is mapped to the freely configurable characteristic. The maximum admissible
setting range of the drive can be set via the frequency limits or percentage limits according to the
configuration selected. In the case of the parameterization of a bipolar characteristic, the set
minimum and maximum limits for both directions of rotation are effective. The percentage values of
the characteristic points are relative to the limits selected.
Parameter
No.
Description
418 Minimum frequency
419 Maximum frequency
The factory settings depend on the setup of parameter
1)
3.50 Hz in configurations 1xx, 4xx;
2)
0.00 Hz in configurations 2xx, 5xx
The control system uses the maximum value of the output frequency, which is calculated from the
Maximum Frequency
define the speed range of the drive, and the percentage values supplement the scaling of the analog
input characteristic in accordance with the functions configured.
Parameter
No.
Description
518 Minimum Reference Percentage
519 Maximum Reference Percentage

16.1.1.3 Tolerance Band and Hysteresis

The analog input characteristic with change of sign of the reference value can be adapted by the
parameter
Tolerance Band
passage of the speed relative to the analog control signal. The parameter value (percent) is relative
to the maximum current or voltage signal.
Parameter
No.
Description
450 Tolerance Band
pos. maximum value
0 V
(0 mA)
(X1/Y1)
neg. maximum value
Without tolerance band
The default
Minimum Frequency
parameterized tolerance band to the hysteresis.
170
419 and the compensated slip of the drive mechanism. The frequency limits
0.00%
0.00%
450 of the application. The adjustable tolerance band extends the zero
0.00%
(X2/Y2)
+10 V
(+20 mA)
418 or
Operating Instructions ACU
Setting
Min.
Max.
0.00 Hz
599.00 Hz
0.00 Hz
599.00 Hz
30
:
Configuration
Setting
Min.
Max.
300.00%
300.00%
Setting
Min.
Max.
25.00%
pos. maximum value
0 V
(0 mA)
(X1/Y1)
neg. maximum value
With tolerance band
Minimum Reference Percentage
Factory setting
1)
3.50 Hz
2)
0.00 Hz
50.00 Hz
Factory setting
0.00%
100.00%
Factory setting
2.00%
(X2/Y2)
+10 V
(+20 mA)
zero point
tolerance band
518 extends the
12/16