16.3.8

Warning mask

The warning mask signals, via a digital signal, if a pre-configured warning is present. The warning
mask is configured via
combined. This enables internal or external control using a common output signal. The display of
269
and 275
Warning
Select one of the settings 1 ... 43 to activate messages.
Select one of the Operation Modes 101 ... 143, if certain warnings are not to be reported.
Create Warning Mask 536
0 -
No change
1 -
Activate everything
2 -
Activate all warnings
3 -
Activate all controller states
10 -
Warning Ixt
11 -
Warning short-term Ixt
12 -
Warning long-term Ixt
Warning heat sink
13 -
temperature
14 -
Warning inside temperature
15 -
Warning limit
16 -
Warning Init
17 -
Motor temperature warning
Warning
18 -
Mains Failure
Warning
19 -
Motor Protection
20 -
Warning Fmax
Warning
21 -
Analog Input MFI1A
Warning
22 -
Analog Input EM-S1INA
Warning
23 -
System Bus
24 -
Warning Udc
25 -
Warning, application
Controller
30 -
Udc Dynamic Operation
31 -
Controller shutdown
32 -
Controller mains failure
33 -
Controller Udc limitation
12/16
Create Warning Mask
is not influenced via the warning mask.
Controller Status
Configured warning mask is not modified.
The warnings and controller status messages stated are linked in
the warning mask.
The warnings reports stated are linked in the warning mask.
The controller status reports stated are linked in the warning
mask.
The frequency inverter is overloaded
Overload reserve for 1 s minus the Warning Limit Short Term
Ixt 405 was reached.
Overload reserve for 60 s minus the Warning Limit Long Term
Ixt 406 was reached.
Max. heat sink temperature TK of 80 °C minus the Warning Limit
Heat Sink Temp. 407 was reached.
Max. Inside Temperature T
Inside Temp. 408 reached.
The controller stated in Controller Status 355 limits the
reference value.
Frequency inverter is being initialized
Waring behavior as per configured Motor Temp. Operation Mode
570 at max. motor temperature T
Phase Supervision 576 reports mains failure.
Operation Mode 571 for motor circuit breaker was triggered.
The Maximum Frequency 419 was exceeded. The frequency
limitation is active
The input signal is lower than 1V/2mA according to the
operation mode Error/Warning Behavior 453.
The input signal at the analog input of an extension module is
lower than 1V/2mA according to the operation mode
Error -/Warning Behavior 453.
A slave on the system bus reports a fault;
warning is only relevant with the EM-SYS option.
The DC link voltage has reached the type-dependent minimum
value.
A warning application is signaled.
Controller is active according to the Operation Mode 670 for the
voltage controller.
The output frequency in the case of a power failure is below the
Shutdown threshold 675.
Failure of the mains voltage and power regulation active
according to Operation Mode 670 for the voltage controller.
The DC link voltage has exceeded the Reference DC-Link
Limitation 680.
Operating Instructions ACU
536. Warnings and controller status messages can be
Function
of 65 °C minus Warning Limit
i
PTC .