In the following settings, the starting current impression is used for the starting behavior:
Configuration
Operation Mode
Configuration
Configuration
motor

13.1.1.2 Frequency Limit

The
623 is impressed in configurations 1xx, 4xx and 6xx for control of the relevant
Starting Current
configuration until the
frequency limit are only permissible if forced-ventilated motors are used.
The transition to the control method of the selected
frequency limit.
The
Frequency Limit
oriented configurations 4xx and 6xx. In V/f control configuration 1xx, parameter
624 is not changed during guided motor commissioning.
Parameter
No.
Description
624 Frequency Limit

13.1.1.3 Brake release time

In order to protect the motor holding brake against damage, the motor may only start after the
brake has been released. Startup to reference speed is effected only after the
625 has elapsed. The time should be set such that it is at least as long as the time required for
releasing the holding brake. By using negative values for the parameter, release of the brake is
delayed. This can be done in order to prevent loads from falling down, for example.
Parameter
No.
Description
625 Brake Release Time
13.1.2

Flux formation

Field-oriented control in the configurations 2xx and 4xx are based on separate regulation of the flux-
forming and torque-forming current components. Upon startup, the machine is magnetized and a
current is impressed first. With parameter
current I
is set. With parameter
sd
time is set.
The current impression is done until the reference value of the rated magnetizing current is reached
or the
Max. Flux-Formation Time
Parameter
No.
Description
780 Max. Flux-Formation Time
781 Current during flux formation
The factory setting of parameter
30:
Configuration
1)
Configurations 1xx
2)
Configurations 2xx/4xx
3)
Configurations 6xx
134
30 = 1xx (V/f control of asynchronous motor),
620 =2, 4, 12 or 14
30 = 4xx (FOR of an asynchronous motor)
30 = 6xx (PSM: sensor-less, field-oriented control - DMR), synchronous
624 is reached. Permanent operating points below the
Frequency Limit
624 is set automatically during guided motor commissioning in the field-
Current during Flux-Formation
Max. Flux-Formation Time
780 is exceeded.
Max. Flux-Formation Time
Operating Instructions ACU
Configuration
Setting
Min.
Max.
0.00 Hz
100.00 Hz
Setting
Min.
Max.
-5000 ms
5000 ms
780 the maximum current impression
Setting
Min.
Max.
1 ms
10000 ms
0.1I
oI
FIN
30 takes place above the
Frequency Limit
Factory setting
2.60 Hz
Brake Release Time
Factory setting
0 ms
781, the magnetization
Factory setting
300 ms
1000 ms
50 ms
I
FIN
FIN
780 depends on parameter
1)
2)
3)
12/16