Operation Mode Liquid Level 1, Parameter Operation Mode 440 = 2
This operation mode can be used, for example, for Liquid Level control.
If the actual value is missing, the function brings the output frequency to an adjustable value.
The minimum value monitoring prevents an acceleration of the drive if the actual value is missing.
If the actual value is missing (< 0.5%) the output frequency is guided to the
441.
Fixed Frequency
This is done using the set
421.
Deceleration (Clockwise)
441 must be in the range between
418 and
The Fixed Frequency
Minimum Frequency
Maximum
419. If the
441 is smaller than the
418, the
Frequency
Fixed Frequency
Minimum Frequency
output frequency is guided to the
418. The frequency will not drop below the
Minimum Frequency
418.
Minimum Frequency
If the actual value is available again, the controller continues operation automatically. The integral
component is reset once the actual value is restored.