System features
8.4 Response times
8.4.9
Control of Extended Functions without encoder via TM54F (CU310-2 and
CU320-2)
The table below shows the response times
until the response is initiated.
Table 8- 9
Response times for control via TM54F
Fu n ction
STO
SBC
SS1
(speed controlled/time and acceleration
controlled),
SS1E (time controlled)
SBR or SAM (limit value violation until STO
is active)
SLS speed limit violated
SSM
SDI (limit value violation
until braking is initiated)
The specified response times are valid for Extended Functions with and without selection!
1)
Start phase: This describes the behavior after switching on (ON command with previously deleted pulses).
2)
Standard: This behavior applies when the pulses have already been enabled.
There is a different behavior, because with the aid of p9586, the encoderless actual value acquisition after pulse enable
can only be activated with a delay.
For CU310-2, use the parameter p10017 of the drive object "TM54F_xx" to calculate the response time, not that of the
3)
control unit.
E x tension of t he response t imes for S LS without encoder or SDI without encoder under
c ertain circumstances
If the safety functions SLS without encoder or SDI without encoder are already selected
when the gating pulses for the Power Module are enabled, then during the starting phase, it
is absolutely imperative that you take into account the response times when limit values are
violated and for system errors in order to extend the time value set in parameter p9586
with respect to the standard values (see the table above).
After the time interval set in parameter p9586, the standard response times apply (see table
above).
360
D rive system has no fault
3,5 x p9500 + r9780 + p10017
3,5 x p9500 + 2 x r9780 + p10017
1 ms
3,5 x p9500 + p10017
3 x p9500 + +r9780 + p9587 + 4 ms
Standard
3 x p9500 + p9587 + 6 ms
3)
2)
Start phase
3 x p9500 + p9587 + p9586
2)
4 x p9500 + p9587 + 4 ms
Standard
2,5 x p9500 + p9587 + 6 ms
2)
Start phase
2,5 x p9500 + p9587 + p9586
2)
CA UTION
from the occurrence of a signal at the terminals
1)
Wo rst ca se fo r
A fa ult is present
+ 1 ms 4 x p9500 + 2 x r9780 + p10017
3)
1 ms
+
4 x p9500 + 6 x r9780 + p10017
3)
1 ms
+ 3 ms
4 x p9500 + p10017
3)
3,5 x p9500 + r9780 + p9587 +
32 ms
4,5 x p9500 + r9780 + p9587 +
32 ms
+ 6 ms
4,5 x p9500 + r9780 + p9587 +
2)
p9586
4,5 x p9500 + p9587 + 32 ms
4 x p9500 + r9780 + p9587 + 32 ms
+ 6 ms 4 x p9500 + r9780 + p9587 + p9586
2)
+ 32 ms
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
+ 3 ms
3)
+ 32 ms
2)
2)
Safety Integrated
+
3)
+
3)
2)