F-Di/F-Do Configuration - Siemens Sinamics S120 Function Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Commissioning
6.8 Commissioning CU310-2 using STARTER/SCOUT
6.8.2

F-DI/F-DO configuration

F-DIs to c ontrol the Extended Functions
This setting option is only available when controlling Extended functions via the onboard
terminals.
Image 6-8
NC/ NO contact (p10040)
Terminal property F-DI 0-2 (p10040.0 = F-DI 0, ... p10040.2 = F-DI 2), only the property of
the second (lower) digital input is set. Always connect an NC contact to digital input 1
(upper). The 2nd digital input can be configured as a NO contact.
LE D s ymbol in t he F-DI screen
The LED symbol after the AND element indicates the logical state (inactive: gray, active:
green, discrepancy error: red).
284
F-DIs to control the Extended Functions screen from
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Safety Integrated