● "Remaining time until test stop"
This indicates the remaining time until dynamic operation and test of the safety switch-off
signal paths are performed (p9660).
● "Shutdown paths require testing"
Select the parameters to be interconnected with the status "Shutdown path test required"
(r9773.31). One or more interconnections are possible, but not mandatory.
● Click "Close" to return to the "Safety Integrated" dialog box.
Not e
Duplicating safety parameters
For safety reasons, when using the STARTER commissioning tool (or SCOUT), you can only
set the safety-related parameters of the first channel offline.
To set the safety-related parameters of the second channel, proceed as follows:
• Activate the "Copy parameters after download" checkbox and then establish an online
connection to the drive unit. Perform the download and then adapt the checksums.
Execute the "Copy RAM to ROM" command and then a POWER ON.
• Or establish an online connection to the drive unit first and then duplicate the parameters
by clicking the "Copy parameters" button on the start screen of the configuration.
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Commissioning
6.7 Commissioning: Basic procedure