Commissioning

6.5 Forced dormant error detection (test stop)

6.5
Forced dormant error detection (test stop)
To fulfill the requirements of standards DIN EN ISO 13849-1 and IEC 61508 regarding timely
error detection, the converter must regularly test its safety-relevant circuits to ensure that
they function correctly – this must be performed at least once every year. The converter
monitors the regular testing of its safety-related circuits, which monitor the speed of the
motor and which safely interrupt the torque-generating energy supply to the motor by means
of safe pulse suppression.
Image 6-1
Table 6- 2
Extended Functions
r9765 contains the remaining monitoring time.
The converter signals that the monitoring time
has come to an end with alarm A01697.
Setting forced dormant error detection (test stop)
If you only use the "Basic Functions", you must take the following steps during
commissioning:
1. Set monitoring time p9659 to a value to match your application.
2. Evaluate the warning A01699 in your higher-level control, e.g. r9773.31 with a digital
output or a bit in the status word of the field bus.
The circuits of "Basic Functions" are part of the circuits of "Extended Functions". If you use
the "Extended Functions", you must take the following steps during commissioning:
1. Set monitoring time p9559 to a value to match your application.
2. Set the monitoring time p9659 to the maximum value.
3. Evaluate alarm A01697 in your higher-level controller, for example by interconnecting the
output of the time monitoring (r9723.0) with a digital output or a bit in the status word of
the fieldbus.
226
Monitoring of regular forced dormant error detection (test stop) in the converter
Monitoring forced dormant error detection (test stop)
Ba sic Functions
r9660 contains the remaining monitoring time.
The converter signals that the monitoring time
has come to an end with alarm A01699.
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6