Acceptance test for Safe Brake Control with encoder (Extended Functions)
N o .
N o te:
The acceptance test must be individually performed for each configured control.
The control can be realized via TM54F, onboard terminals (CU310-2) or via PROFIsafe.
1.
Initial state
Drive in the "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
Safety configured with encoder (p9506 = 0 or p9506 = 2)
SBC function enabled (p9602 = 1)
Brake as in sequence control or brake always released (p1215 = 1 or p1215 = 2)
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if used); see note "Non-critical alarms" at the beginning of Section "Acceptance
test."
r9773.4 = 0 (SBC not requested)
r9720.0 = 1 (STO deselected) or r9720.1 = 1 (SS1 deselected)
r9722.0 = 0 (STO inactive)
2.
Run drive (if applied, brake is released)
Check whether the correct drive is operational
Select STO when you issue the traversing command and check the following:
Brake is applied
No safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if one is being used)
r9773.4 = 1 (SBC requested)
r9720.0 = 0 (STO selected) or r9720.1 = 0 (SS1 selected)
r9722.0 = 1 (STO active)
3.
Deselect STO and check the following:
No safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if one is being used)
r9720.0 = 1 (STO deselected) or r9720.1 = 1 (SS1 deselected)
r9722.0 = 0 (STO active)
4.
Acknowledge switch-on inhibit and run the drive. Check whether the correct drive is operational.
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
D e scri p ti o n
A.3 Acceptance tests (recommendations)
Appendix
Sta tu s
431