Siemens Sinamics S120 Function Manual page 484

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Appendix
A.3 Acceptance tests (recommendations)
N o .
5.
Save/print the trace and add it to the acceptance report (refer to the example below)
6.
Canceling SS1
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if one is being used)
Acknowledge switch-on inhibit and run the drive
Note: After deselecting STO, the drive must be switched on within 5 seconds.
Check whether the correct drive is operational
Ex ample trace: SS1 (without encoder)
Drive_1.r9714[0]: SI motion diagnostics velocity, load-side velocity actual value at the Control Unit
Drive_1.r9714[1]: SI motion diagnostics velocity, actual SBR velocity limit at the Control Unit
SS1 active
STO active
Deselect SS1
Image A-17
Example trace: SS1 (without encoder)
484
D e scri p ti o n
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Sta tu s
Safety Integrated