Control of the safety functions

5.1

Control possibilities

The following options for controlling Safety Integrated functions are available:
Table 5- 1
Basic
Functions
Extended
Functions
Only the F-DI 0 can be used for the control. The F-DO is not available.
1)
Not e
P ROFIsafe or TM54F
Using a Control Unit, control is possible either via PROFIsafe or TM54F. Mixed operation is
not permissible.
The safety-oriented input and output terminals (F-DI and F-DO) act as an interface between
the SINAMICS S120 Safety Integrated functionality and the process.
A dual-channel signal applied to an F-DI (Fail-safe Digital Input, safety-oriented digital input
= safe input terminal pair) controls the active monitoring of the activation/deactivation of
safety functions.
An F-DO (Fail-safe Digital Output, safety-oriented digital output = safe output terminal pair)
delivers a dual-channel signal representing feedback from the safety functions.
Dual-channel processing of I/O signals
A dual-channel structure is implemented for data input/output and for processing safety-
oriented I/O signals. All requests and feedback signals for safety-oriented functions should
be entered or tapped using both channels.
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Controlling the Safety Integrated functions
Te rminals (on the
C o ntrol Unit and Mo-
to r/Power Module)
Yes
No
PR OFIsafe based
TM5 4F
o n PROFIBUS or
PR OFINET
Yes
Yes
Yes
Yes
5
C o ntrol
On board
w i thout
F-D I/F-DO
se lection
(C U310-2)
No
Yes
1)
SLS, SDI
Yes
167