N o .
As soon as r9713[0] leaves the tolerance window, a safety message becomes active
(r9722.7 = 0)
As a consequence, the drive is brought to a standstill with STOP B and STOP A
5.
Save/print the trace and add it to the acceptance report (refer to the example below)
6.
Deselect SOS and acknowledge safety messages
No safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if one is being used)
Acknowledge switch-on inhibit and run the drive
Check whether the drive is moving
Ex ample trace: SOS
Drive_1.r9713[0]: SI motion diagnostics position actual value load side, load-side actual value on the Control Unit
Internal event
SOS active
SS1 active
STO active
STOP A or B
Deselect SOS
Image A-3
Example trace: SOS
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6