A.3 Acceptance tests (recommendations)
N o .
C01715 (10), C30715 (10); SLP1 violated, or
C01715 (20), C30715 (20); SLP2 violated
C01710, C30710 (STOP E initiated)
C01707, C30707 (tolerance for safe operating stop exceeded)
C01701, C30701 (STOP B initiated)
C01700, C30700 (STOP A initiated)
4.
Analyze trace:
As soon as r9708[0] leaves the SLP limits, a safety message becomes active
(r9722.7 = 0).
If the upper SLP limit is violated, the safety message "SLP upper limit not main-
tained" becomes active (r9722.30 = 0).
If the lower SLP limit is violated, the safety message "SLP lower limit not main-
tained" becomes active (r9722.31 = 0).
STOP E is initiated as a consequence.
As a consequence of STOP E (selection SOS) the above-described responses will
be triggered if the drive is not stopped by the drive-based ESR function or higher-
level controller when STOP E is activated
5.
Save/print the trace and attach to the acceptance report
6.
Repeat points 1 to 6 for the opposite SLP limit.