Siemens Sinamics S120 Function Manual page 404

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Appendix
A.3 Acceptance tests (recommendations)
● Test of the SI function "Safe Operating Stop" (SOS)
– For this purpose, a trace recording of individual parameters can be used.
● Test of the SI function "Safely-Limited Speed" (SLS)
– For this purpose, a trace recording of individual parameters can be used.
● Test of the SI function "Safe Direction" (SDI)
– For this purpose, a trace recording of individual parameters can be used.
● Test of the SI function "Safe Speed Monitor" (SSM)
– For this purpose, a trace recording of individual parameters can be used.
● Test of the SI function "Safely-Limited Position" (SLP)
– For this purpose, a trace recording of individual parameters can be used.
C) Functional t esting of f orced dormant error detection (test stop)
Test of the forced dormant error detection (test stop) of the safety functions on each drive
(for the Basic and/or Extended Functions) and the TM54F (if used).
● Test of the forced dormant error detection (test stop) of the safety function on the drive
– If you are using Basic Functions, you need to activate and then deactivate STO once
– If you are using Extended Functions, you need to perform forced dormant error
● Forced dormant error detection (test stop) of the TM54F (if available)
– Perform forced dormant error detection (test stop) of the TM54F
● Forced dormant error detection (test stop) of the CU310-2 (if available)
– Perform forced dormant error detection (test stop) of the CU310-2
D) Conc lusion of the report
Report of the commissioning status tested and countersignatures
● Inspection of SI parameters
● Logging of checksums (for each drive)
● Issuing of the safety password and documenting this process (do not specify the safety
password in the report!)
● RAM to ROM backup, upload of project data to STARTER, and backup of the project
● Countersignature