Ap plication
Standard telegram
+ SIC/SCC
Standard telegram
+ free telegram con-
figuration with BICO
+ SIC/SCC
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Action by the u ser
Specify standard telegram; e.g.
p0922 = 106
Select SIC/SCC; e.g. p60122 = 701
Define standard telegrams with pos-
sible telegram extension; e.g. p0922
= 999 and p2079 = 106
Reserve space for the telegram
extension with free BICO wiring, e.g.
2 words in the receive direction and
1 word in the send direction:
p2070 = 11 + 2 = 13
p2071 = 15 + 1 = 16
Select SIC/SCC; e.g. p60122 = 701
Control of the safety functions
5.8 Safety Info Channel and Safety Control Channel
Effect
p2079 = p0922 = 106
r2050 and p2051 are appropriately preassigned
and completely locked so that changes cannot be
made.
In p2070 and p2071, the number of trans-
mit/receive words are occupied and cannot be
changed (e.g: p2070 = 11 and p2071 = 15).
The telegram extension for SCC/SIC is directly
attached to the standard telegram in r2050 and
p2051.
r2050 and p2051 are appropriately preassigned.
Areas that are not preassigned, can be freely inter-
connected.
p2070 = 11, p2071 = 15 are preassigned corre-
sponding to p0922 and cannot be changed.
Words r2050[11...12] and p2051[15] are reserved
for the telegram extension and can be freely inter-
connected.
The telegram extension for SIC/SCC is inserted
from r2050[13...] and p2051[16...].
In r2050 and p2051, the words for SIC/SCC are
preassigned accordingly and locked. The other
words can be freely connected.