Acceptance mode
● Click "Acceptance mode" in the "Safety Integrated" dialog box to parameterize
acceptance:
● This dialog box offers the following setting options for the acceptance mode:
– "Acceptance mode time limit"
– "Activate acceptance mode"
● Click "Close" to return to the "Safety Integrated" dialog box.
Completion
● After parameter assignment, you must save the data and duplicate the values for the
second channel.
Not e
Duplicating safety parameters
For safety reasons, when using the STARTER commissioning tool (or SCOUT), you can
only set the safety-related parameters of the first channel offline.
To set the safety-related parameters of the second channel, proceed as follows:
• Activate the "Copy parameters after download" checkbox and then establish an online
• Or establish an online connection to the drive unit first and then duplicate the
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
You can enter the maximum time for the acceptance test mode (p9558) here.
Click this button to activate the acceptance mode.
connection to the drive unit. Perform the download and then adapt the checksums.
Execute the "Copy RAM to ROM" command and then a POWER ON.
parameters by clicking the "Copy parameters" button on the start screen of the
configuration.
Commissioning
6.7 Commissioning: Basic procedure
265