Control Via Tm54F - Siemens SINAMICS S120 Function Manual

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Function
SS1/SS1E (time-controlled)
Selection until SBC is initiated
SS1 (time-controlled)
Selection until braking is initiated
The specified response times involve internal SINAMICS response times. Program run times in the F-host and the
1)
transmission time via PROFIBUS or PROFINET are not taken into account. When calculating the response times be-
tween the F-CPU and the converter, you must take into account that faults in the communication can result in a safety
function only being selected after the PROFIsafe monitoring time (F_WD_Time) has expired. The PROFIsafe monitoring
time (F_WD_Time) must also be included in the calculation when an error occurs.
t_K is the time for internal communication within the SINAMICS module; t_K can be determined as follows:
2)
For isochronous communication
For non-isochronous communication
p2048 is applicable for communication via IF1, p8848 for communication via IF2.
3)
10.7.3

Control via TM54F

The following table lists the response times from the control via TM54F until the response
actually occurs.
Table 10- 4
Response times for control via TM54F
Function
STO
SBC
SS1/SS1E (time-controlled)
Selection until STO is initiated
SS1/SS1E (time-controlled)
Selection until SBC is initiated
SS1 (time-controlled)
Selection until braking is initiated
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Drive system has no fault
6 · r9780 + p9652 + t_K
2)
5 · r9780 + 2 ms + t_K
2)
t_K = To (for To, see parameter r2064[4])
t_K = 4 ms
(for modules on which p2048 or p8848
t_K = value from p2048 or p8848
(for modules, on which p2048 or p8848
Drive system has no fault
3 · r9780 + p10017 + 2 ms
4 · r9780 + p10017 + 2 ms
3 · r9780 + p9652 + p10017 + 2 ms
4 · r9780 + p9652 + p10017 + 2 ms
3 · r9780 + p10017 + 4 ms
Safety Integrated Basic Functions
10.7 Response times
Worst case for
A fault is present
10 · r9780 + p9652 + t_K
5 · r9780 + 2 ms + t_K
do not exist)
3)
3)
exist)
3)
Worst case for
A fault is present
3 · r9780 + p10017 + 2 ms
8 · r9780 + p10017 + 2 ms
3 · r9780 + p9652 + p10017 + 2 ms
8 · r9780 + p9652 + p10017 + 2 ms
3 · r9780 + p10017 + 4 ms
2)
2)
695