Cont rol of the safety functions
5.3 Activation via PROFIsafe
Safety status word 2 (S_ZSW2)
S_ZSW2, input signals
see function diagram [2843].
Table 5- 10
Description of safety status word 2 (S_ZSW2)
Byte
Bi t
0
0
1
2
3
4
5
6
7
1
0
1
2
3
4
5
6
7
186
Me a n i n g
STO active
SS1 active
SS2 active
SOS active
SLS active
Reserved
SLP active
Internal Event
Reserved
Active SLS level bit 0
Active SLS level bit 1
Reserved
SDI positive active
SDI negative active
Reserved
SSM (speed)
R e m a rks
1
STO active
0
STO not active
1
SS1 active
0
SS1 not active
1
SS2 active
0
SS2 not active
1
SOS active
0
SOS not active
1
SLS active
0
SLS not active
1
SLP active
0
SLP not active
The status signal "SLP active" is not the same
as the diagnostic signal "SLP active" (r9722.6),
but is the AND logic operation of "SLP active"
(r9722.6) and "safely referenced" (r9722.23).
1
Internal event
0
No internal event
Display of the velocity limit for SLS (2 bits)
1
SDI positive active
0
SDI positive not active
1
SDI negative active
0
SDI negative not active
1
SSM (speed below limit value)
0
SSM (speed higher than/equal to limit)
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6