Appendix
A.3 Acceptance tests (recommendations)
SLP with stop response "STOP C"
N o .
N o te:
The acceptance test must be individually performed for each configured control and for both limits.
Control can be realized via TM54F, onboard terminals (CU310-2) or via PROFIsafe.
1.
Initial state
Drive in the "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
Safety configured with encoder (p9506 = 0 or p9506 = 2)
SLP enabled (p9501.1 = 1)
SLP deselected (r9720.6 = 1)
Drive safely referenced (r9721.7 = r9722.23 = 1)
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if used); see note "Non-critical alarms" at the beginning of Section "Ac-
ceptance test."
2.
It may be necessary to take measures in the higher-level controller to be able to exceed the position limits.
3.
Configure and activate trace recording
Trigger: Trigger on variable - bit pattern (r9722.7 = 0)
Record the following values: r9708[0], r9713[0], r9721, r9722
Select the time interval and pretrigger so you can recognize when the active SLP
limits have been exceeded and the subsequent drive responses
For better analysis, display the following bit values:
r9722.2 (SS2 is active, is set with STOP C); r9722.3 (SOS active)
r9721.13 (STOP C active)
r9722.7 (internal event; set to 0 when the first safety message occurs)
r9722.6 (SLP active)
r9722.30 (SLP limit high maintained)
r9722.31 (SLP limit low maintained)
Select SLP traversing range
Traverse the drive to a safe absolute position within this traversing range
Select SLP
Switch-on the drive and traverse in the negative or positive direction of rotation
Check whether the drive is moving, and after the upper or lower SLP limit (p9534 or
p9535) has been exceeded, that it is braked to a standstill along the OFF3 ramp
Check whether the following safety messages are pending:
C01715 (10), C30715 (10); SLP1 violated, or
C01715 (20), C30715 (20); SLP2 violated
474
D e scri p ti o n
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Sta tu s
Safety Integrated