N o .
Drive safely referenced (r9721.7 = r9722.23 = 1)
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if used); see note "Non-critical alarms" at the beginning of Section "Ac-
ceptance test."
2.
It may be necessary to take measures in the higher-level controller to be able to exceed the position limits.
3.
Configure and activate trace recording
Trigger: Trigger on variable - bit pattern (r9722.7 = 0)
Record the following values: r9708[0], r9713[0], r9720, r9721, r9722
Select the time interval and pretrigger so you can recognize when the active SLP
limits have been exceeded and the subsequent drive responses
For better analysis, display the following bit values:
r9721.12 (STOP A or B active)
r9722.1 (SS1 active; set for STOP B)
r9722.7 (internal event; set to 0 when the first safety message occurs)
r9722.6 (SLP active)
r9722.30 (SLP limit high maintained)
r9722.31 (SLP limit low maintained)
Select SLP traversing range
Traverse the drive to a safe absolute position within this traversing range
Select SLP
Switch-on the drive and traverse in the negative or positive direction of rotation
Check whether the drive is moving, and after the SLP limit (p9564) has been ex-
ceeded that it is braked along the OFF3 ramp before STOP A becomes active
Check whether the following safety messages are pending:
C01715 (10), C30715 (10); SLP1 violated, or
C01715 (20), C30715 (20); SLP2 violated
C01701, C30701 (STOP B initiated)
C01700, C30700 (STOP A initiated)
4.
Analyze trace:
As soon as r9708[0] leaves the SLP limits, a safety message becomes active
(r9722.7 = 0).
If the upper SLP limit is violated, the safety message "SLP upper limit not main-
tained" becomes active (r9722.30 = 0).
If the lower SLP limit is violated, the safety message "SLP lower limit not maintained"
becomes active (r9722.31 = 0).
STOP B is initiated as a consequence (with subsequent stop STOP A)
5.
Save/print the trace and attach to the acceptance report
6.
Repeat points 1 to 6 for the other position limit.
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
D e scri p ti o n
A.3 Acceptance tests (recommendations)
Appendix
Sta tu s
473