Description of Safety Integrated functions
4.2 Safety Integrated Extended Functions
Restart after OFF2/STO
If the drive has been switched off via STO, the following steps need to be carried out before
a restart can be performed:
1st
case
2nd
case
3rd
case
4th
case
104
State after switching on
SLS selected
STO selected
Pulse suppression active
Deselect STO
The drive enable must be issued within 5 seconds via a positive edge at OFF1, other-
wise STO is reactivated.
Situation
Traversing to standstill with SLS selected
OFF1 is initiated, pulse cancellation becomes active (internal selection
STO)
Select STO
Deselect STO
STO activated internally via pulse suppression: This activation must be undone by selec-
tion/deselection.
The drive enable must be issued within 5 seconds via a positive edge at OFF1, other-
wise STO is reactivated.
Situation
Traversing to standstill with SLS selected
OFF1 is initiated, pulse cancellation becomes active (internal selection
STO)
Deselect SLS
STO activated internally via pulse suppression: This activation must be undone by se-
lecting/deselecting SLS.
Select SLS
The drive enable must be issued with a positive edge at OFF1 within 5 seconds, other-
wise STO is reactivated.
Situation
All Safety Integrated functions are deselected.
After this the drive enable must be given by a positive edge at OFF1.
In this case, the motor is not started safely.
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6