What do you have to set for communication via PROFINET

Configuring PROFINET communication in the I/O controller
You require the appropriate engineering system for the IO controller to configure PROFINET
communication in the IO controller.
If required, load the GSDML file of the converter into the engineering system.
Device name
In addition to the MAC address and IP address, PROFINET also uses the device name to
identify PROFINET devices (Device name). The device name must be unique across the
PROFINET network.
To assign the device name, you need an engineering software, e.g. Startdrive.
The converter saves the device name in its EEPROM. If an optional memory card is inserted,
the converter saves the device name additionally on the memory card.
IP address
In addition to the device name, PROFINET also uses an IP address.
You have the following options to specify the IP address of the converter:
• You specify the IP address via an engineering software tool, e.g. Startdrive.
• The IO Controller assigns an IP address to the converter.
The converter saves the IP address in its EEPROM. If an optional memory card is inserted, the
converter saves the IP address additionally on the memory card.
Telegram
Set the same telegram in the converter as in the IO Controller. Interconnect the telegrams in
the control program of the IO Controller with the signals of your choosing.
Application examples
You can find application examples for PROFINET communication on the Internet:
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(https://support.industry.siemens.com/cs/ww/en/view/60441457)
Controlling the speed of a SINAMICS G110M/G120 (Startdrive) with S7-1500 (TO) via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(https://support.industry.siemens.com/cs/ww/en/view/78788716)
78
Installing GSDML (Page 79)
Drive control via PROFINET (Page 112)