Wiring
4.13 Connecting to PROFINET and Ethernet
4.13.4

Connecting the converter to PROFINET

Procedure
1. Integrate the converter in the bus system (e.g. ring topology) of the control using PROFINET
cables and PROFINET sockets X150 P1/P2.
The maximum permitted cable length from the previous station and to the next one is
100 m.
2. Externally supply the converter with 24 V DC through interface X01.
You have now connected the converter to the control system via PROFINET.
4.13.5

What do you have to set for communication via PROFINET

Configuring PROFINET communication in the I/O controller
You require the appropriate engineering system for the IO controller to configure PROFINET
communication in the IO controller.
If required, load the GSDML file of the converter into the engineering system.
Device name
In addition to the MAC address and IP address, PROFINET also uses the device name to
identify PROFINET devices (Device name). The device name must be unique across the
PROFINET network.
To assign the device name, you need an engineering software, e.g. Startdrive.
The converter saves the device name in its EEPROM. If an optional memory card is inserted,
the converter saves the device name additionally on the memory card.
IP address
In addition to the device name, PROFINET also uses an IP address.
You have the following options to specify the IP address of the converter:
• You specify the IP address via an engineering software tool, e.g. Startdrive.
• The IO Controller assigns an IP address to the converter.
The converter saves the IP address in its EEPROM. If an optional memory card is inserted, the
converter saves the IP address additionally on the memory card.