Detecting Cable Disconnections; Checking Loopback Execution Status - Mitsubishi Electric QJ71GF11-T2 User Manual

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

(4) Detecting cable disconnections

Cable disconnection is detected using the CC-Link IE Field Network diagnostics as well as link special relays
(SBs) and link special registers (SWs). (
1.
If a cable is disconnected, a baton pass error causes Baton pass status (own station) (SB0047) to
turn on.
2.
30
is stored in Cause of baton pass interruption (SW0048).
H
Details on the causes of error can be checked using link special relays (SBs) and link special registers (SWs)
corresponding to the station number where the error has occurred.
Number
SB0047
Baton pass status (own station)

(5) Checking loopback execution status

Whether loopback is being performed or not can be checked using link special relays (SBs) and link special
registers (SWs). (
1.
While loopback is performed, Loopback status (SB0065) is on.
2.
Loopback station numbers are stored to Loopback station number (SW0070 and SW0071).
No.
SB0065
Loopback status
Loopback when a cable is disconnected between station No. 2 and stations No. 3
Ex.
Station No.0
SW0070 and SW0071 store "2" and "3", respectively.
Remark
If the master station is powered on before slave stations, data link may be reconfigured. During the reconfiguration
(maximum three seconds), an error is detected using SB00B0. (Note that an error is detected for a maximum of 13 seconds
in a master/local module with the serial number (first five digits) of "14041" or earlier.)
Starting up the master station last can prevent data link from being reconfigured.
Page 206, CHAPTER 9)
Description
Page 206, CHAPTER 9)
Description
Station No.1
Number
SW0048
Cause of baton pass interruption
No.
SW0070
Loopback station number 1
SW0071
Loopback station number 2
Station No.2
Station No.3
CHAPTER 11 PROGRAMMING
Description
Description
415
11

Advertisement

Table of Contents
loading