(b) Starting the interrupt program of the master station (station number 0) when the
master station receives data sent from another station using the SEND instruction
The following is a setting example to execute the interrupt program corresponding to the interrupt pointer I52
when the master station (station number 0) receives data sent from the local station (station number 1) using
the SEND instruction in channel 2.
1.
Set the interrupt setting parameters for the master/local module (station number 0) in the
"Interrupt Settings" window as shown below.
2.
Set the parameters in the "Intelligent Function Module Interrupt Pointer Setting" window as shown
below.
112
Master/local module
Master station
CPU module
(Station No.0)
Interrupt program
execution
Channel 1
1
SM400
Channel 2
I52
RECVS
2
3
IRET
1
3
Master/local module
Local station
(Station No.1)
Channel 1
Channel 2
Set the same SI number as the interrupt settings.
CPU module
SEND
2